5)校验热稳定,取后备保护为0.15S
td = tkd + tb = 0.036 + 0.05= 0.086S
tdz = tol+tb=0.086+0.15=0.2366s
Qd = I2×dz = 17.3732×0.2366 = 71.419KA2S
Qr = I2r t = I2r t = 502×4 = 10000KA2S
即Qr > Qd 满足要求
Ir ≥I∞tdz/t = 17.3730.2366/4 = 4.225< 40满足要求
6)检验动稳定:icj≤ idw
icj= 44.301< 100 满足要求
故选择户外LW6-220型SF6断路器能满足要求,由上述计可列出下表:
设备
项目 LW6-220
产品数据 计算数据
Vmax≥Vgmax 252KV 253KV
Ie≥Igmax 3150A 991A
ieg≥ich 100KA 44.301KA
Iekd≥I″ 50KA 17.373KA
idw≥icj 100KA 44.301KA
Qr≥Qd 10000KA2.S 71.419KA2.S
2、110KV侧断路器
考虑到2台主变及一定的交换功率
1)额定电压:Vymax≥Vgmax Vgmax = 1.15×110 = 126.5KV;
2)额定电流:Iy≥Igmax
Igmax= 1.05×2Se 3Vv = 1.05×2×180 3×110 =1.9845KA;
3)按开断电流选择:Iekd≥I″= 11.81KA 即Iekd≥11.81KA;
4)短路关合电流:ieg≥icj = 30.115KA 即ieg≥30.115KA;
根据以上数据可以初步选择LW14-110高压优氟化硫断路器,其参数为:
最高工作电压126KV
额定工作电压110KV
固有分闸时间为0.025S
燃弧时间取0.05s
5)检验热稳定取后备保护为0.15S
td = tkd + tb = 0.025+0.0 5 = 0.075S β″= I″I∞ = 1
tdz=tol+tb=0.075+0.15=0.225s
Qd = I2 dz = 11.812×0.225= 31.38KA2S
Qr = I2r t = 31.52×3 = 3969KA2S
即Qr > Qd 满足要求
检验动稳定:icj≤ idw
icj= 30.115<idw= 80满足要求
由以上计算表明选择LW14-110高压优氟化硫断路器能满足要求,列出下表
设备
项目 LW14-110
产品数据 计算数据
Vmax≥Vgmax(kv) 126 126.5
Ie≥Igmax(A) 2000 1984
ieg≥ich(KA) 80 30.115
Iekd≥I″(KA) 31.5 11.81
idw≥icj(KA) 80 30.115
Qr≥Qd( )
2976 31.38
3.110kv侧最大一回负荷出线侧断路器
1)额定电压:Vmax≥Vgmax Vgmax = 1.15×110 = 126.5KV;
2)额定电流:Ie≥Igmax
Igmax= =1.05×40 3×110×0.6 =0.367KA;
3)按开断电流选择:Iekd≥I″=11.81KA 即Iekd≥11.81KA;
4)短路关合电流:ieg≥ich = 30.115KA 即ieg≥30.115KA;
根据以上数据可以初步选择SW4-110高压少油断路器,其参数为:
最高工作电压126KV
额定电压110KV
固有分闸时间为0.05S
燃弧时间取0.05s
5)检验热稳定取后备保护为0.15S
td = tkd + tb = 0.05+0.0 5 = 0.1S
tdz=tol+tb=0.0原文请找腾讯752018766优,文-论'文"网http://www.youerw.com 75+0.15=0.25s
Qd = I2 dz = 11.812×0.25= 34.86KA2S
Qr = I2r t = 31.52×3 = 2969KA2S
即Qr > Qd 满足要求
检验动稳定:icj≤ idw
icj= 30.115<idw= 80满足要求
由以上计算表明选择LW14-110高压优氟化硫断路器能满足要求,列出下表