1、 网络潮流计算(均一网)
发电厂负荷:Samax = 38 + j23.55 MVA Samin= 19+ j14.25 MVA
变电所1:S1ma原文请找腾讯752018766优,文'论'文,网
http://www.youerw.com/ x = 40 + j23.73 MVA S1min= 20 + j13.96 MVA
变电所2:S2max = 18 + j10.2 MVA S2min= 9 + j6.28 MVA
变电所3:S3max = 16 + j9.92 MVA S3min= 8 + j5.79 MVA
变电所4:S4max = 20 + j11.87 MVA S4min= 10 + j7.5 MVA
方案1:
Sa1max = S1max = 40 + j23.73 MVA
Sa2max = S2max = 18 + j10.2 MVA
Sa3max = S3max = 16 + j9.92 MVA
Sa4max = S4max = 20 + j11.87 MVA
方案3:
Sa1max = S1max= 40 + j23.73 MVA
Sa2max = S2max = 18 + j10.2 MVA
Sa3max = [S3max×(L4 + L34)+ S4max×L4]/(L3 + L4 + L34)= 16.4+j9.98 MVA
Sa4max = [S4max×(L3+ L34)+ S3max×L3]/(L3 + L4 + L34)= 19.6+j11.81 MVA
S3-4max=0.4+j0.06 MVA
2、选择导线:
查表得: Tmax = 5000 h Je=1.070A/(mm2)
Tmax = 5300 h Je=1.016 A/(mm2)
Tmax = 5400 h Je=0.998 A/(mm2)
Tmax= 5500 h Je=0.980 A/(mm2)
导体面积A计算公式:
S = Smax/(1.732×110×λ×Je)
方案1的导线截面积:
A1 = 114.07 mm2 A2 = 53.44 mm2
A3 = 49.50 mm2 A4 = 62.28 mm2
根据截面积选取导线:(阻抗单位 )
L1选择双回线LGJ-120:单位阻抗值为0.2345+j0.406;持续容许电流:380A
L2选择双回线LGJ-70 :单位阻抗值为0.4217+j0.426; 持续容许电流:275A
L3选择双回线LGJ-70 :单位阻抗值为0.4217+j0.426; 持续容许电流:275A
L1选择双回线LGJ-70 :单位阻抗值为0.4217+j0.426; 持续容许电流:275A
按照最大可能传输功率的发热校验其截面积:
Imax = Smax/(1.732×110×λ)
I1max = 244A < 380A I2max = 109A < 275A
I3max = 99A < 275A I4max = 122A < 275A
满足要求
方案3的导体截面积:
A1 = 114 mm¬¬¬2 A2 = 54mm2
A3 = 101 mm2 A4= 123mm2
A43 = 3mm2
根据截面积选取导线:(阻抗单位 )
L1选择双回线LGJ-120:单位阻抗值为0.2345+j0.406;持续容许电流:380A
L2选择双回线LGJ-70 :单位阻抗值为0.4217+j0.426; 持续容许电流:275A
L3选择双回线LGJ-120:单位阻抗值为0.2345+j0.406;持续容许电流:380A
L4选择双回线LGJ-150:单位阻抗值为0.1939+j0.400;持续容许电流:445A
L43选择双回线LGJ-70:单位阻抗值为0.4217+j0.426;持续容许电流:275A
按照最大可能传输功率的发热校验其截面积:
S = Smax/(1.732×110×λ)
I1max =244A < 380A I2max = 109A < 275A
I3max =226A < 380A I4max = 226A < 445A
I4—3max =122A<275A
满足要求
3、最大电原文请找腾讯752018766优,文'论'文,网
http://www.youerw.com/ 压降落ΔUmax的校验
技术要求:正常情况下 ΔU% < 10%
故障情况下 ΔU% < 15%
忽略电压降落横向量,按照下边公式计算