Figure 1。1 Simple Relay Layouts and Schematics
Relays are used to let one power source close a switch for another (often high current) power source, while keeping them isolated。 An example of a relay in a simple control application is shown in Figure 1。2。 In this system the first relay on the left is used as normally closed, and will allow current to flow until a voltage is applied to the input A。 The second relay is normally open and will not allow current to flow until a voltage is applied to the input B。 If current is flowing through the first two relays then current will flow through the coil in the third relay, and close the switch for output C。 This circuit would normally be drawn in the ladder logic form。 This can be read logically as C will be on if A is off and B is on。
Figure 1。2 A Simple Relay Controller
The example in Figure 1。2 does not show the entire control system, but only the logic。 When we consider a PLC there are inputs, outputs, and the logic。 Figure 1。3 shows a more complete representation of the PLC。 Here there are two inputs from push buttons。We can imagine the inputs as activating 24V DC relay coils in the PLC。 This in turn drives an output relay that switches 115V AC, that will turn on a light。 Note, in actual PLCs inputs are never relays, but outputs are often relays。 The ladder logic in the PLC is actually a computer program that the user can enter and change。 Notice that both of the input push buttons are normally open, but the ladder logic inside the PLC has one normally open contact, and one normally closed contact。 Do not think that the ladder logic in the PLC need so match the inputs or outputs。 Many beginners will get caught trying to make the ladder logic match the input types。
Figure 1。3 A PLC Illustrated With Relays
Many relays also have multiple outputs (throws) and this allows an output relay to also be an input simultaneously。 The circuit shown in Figure 1。4 is an example of this, it is called a seal in circuit。 In this circuit the current can flow through either branch of the circuit, through the contacts labelled A or B。 The input B will only be on when the output B is on。 If B is off, and A is energized, then B will turn on。 If B turns on then the input B will turn on, and keep output B on even if input A goes off。 After B is turned on the output B will not turn off。
Figure 1。4 A Seal-in Circuit
1。2 Programming
The first PLCs were programmed with a technique that was based on relay logic wiring schematics。 This eliminated the need to teach the electricians, technicians and engineers how to program a computer - but, this method has stuck and it is the most common a technique for programming PLCs today。 An example of ladder logic can be seen in Figure 1。5。 To interpret this diagram imagine that the power is on the vertical line on the left hand side, we call this the hot rail。 On the right hand side is the neutral rail。 In the figure there are two rungs, and on each rung there are combinations of inputs (two vertical lines) and outputs (circles)。 If the inputs are opened or closed in the right combination the power can flow from the hot rail, through the inputs, to power the outputs, and finally to the neutral rail。 An input can come from a sensor, switch, or any other type of sensor。 An output will be some device outside the PLC that is switched on or off, such as lights or motors。 In the top rung the contacts are normally open and normally closed。 Which means if input A is on and input B is off, then power will flow through the output and activate it。 Any other combination of input values will result in the output X being off。
Figure 1。5 A Simple Ladder Logic Diagram
The second rung of Figure 1。5 is more complex, there are actually multiple combinations of inputs that will result in the output Y turning on。 On the left most part of the rung, power could flow through the top if C is off and D is on。 Power could also (and simultaneously) flow through the bottom if both E and F are true。 This would get power half way across the rung, and then if G or H is true the power will be delivered to output Y。 In later chapters we will examine how to interpret and construct these diagrams。 PLC自动化制造系统英文文献和中文翻译(2):http://www.youerw.com/fanyi/lunwen_97058.html