摘 要:谐波电流检测环节是有源电力滤波器的重要组成部分,对其进行研究具有重要的意义。本文首先介绍了三相四线制系统中常用的谐波电流检测方法:FBD算法、ip-iq算法、p-q-r算法、TTA算法;其次重点分析了FBD电流检测法与p-q-r电力系统谐波检测法,并给出仿真模型;最后通过在有效性、准确性、时效性、计算量等方面比较两种算法的优劣,并给出结论。78266
毕业论文关键词:三相四线制,p-q-r算法,ip-iq算法,FBD算法,TTA算法,谐波检测
Abstract:Harmonic current detection is an important part of active power filter, and its research is of great significance。 In this paper, we first introduce the three-phase four wire system commonly used harmonic current detection method: FBD algorithm, IP IQ algorithm, p-q-r algorithm, TTA algorithm; secondly focuses on the analysis of the FBD current detection method and p-q-r power system harmonic detection method, and the corresponding simulation model。 Finally, the in effective, accuracy, timeliness of calculation amount and terms of comparison of the two algorithms the pros and cons, and the conclusion is given。
Keywords: three phase four-wire system,P-Q-R algorithm ,IP-IQ algorithm ,FBD algorithm ,TTA algorithm ,Harmonic detection
目 录
1 绪论 3
1。1 谐波的产生及危害 3
1。2有源电力滤波器的基本原理 3
1。3 本课题研究的内容 4
2几种基于常见的三相四线制谐波电流检测算法 4
2。1 FBD电流检测法 4
2。2 ip-iq谐波检测方法 5
2。3基于p-q-r法的电力系统谐波检测方法 11
2。4 TTA谐波电流检测算法 15
3 FBD电流检测法与p-q-r电力系统谐波检测法的分析比较 18
3。1谐波电流检测准确性 20
3。2消除中线电流的有效性 20
3。3计算量 20
3。4 实时性 20
结论 20
参 考 文 献 22
致 谢 23
1 绪论
现代科技的高速发展,导致电力系统中的用电负荷结构发生了很大的变化,电力电子变流装置的应用变得日益广泛,虽然这些技术使得电能获得了更加充分的利用,但是广泛使用非线性电力装置设备不可避免地产生了大量畸变的电流谐波,畸变电流在电网中的流动导致了谐波电压地产生,因而系统安全、稳定、经济运行时时被谐波污染所威胁,这给同一网络的线性负载与其它用户带来极大的影响。目前,谐波己成为污染电力系统的严重公害之一,人们纷纷将关注放在处理电力系统谐波问题上。因此采取有效措施来检测谐波,进而抑制谐波,减少谐波危害变得尤为重要。
1。1 谐波的产生及危害论文网
谐波的产生:谐波产生的根本原因是,当电流流经负载时,与所加的电压不呈线性关系,形成了非正弦电流,从而产生谐波。电网中各种电力电子设备、变压器、发电机、电弧炉和荧光灯等都是谐波源。在电力电子器件大规模使用前,电力系统自身就包含大量的产生谐波的非线性元器件。电力电子器件大规模使用后,电力电子装置成为主要的谐波源。