    However, its greatest application has been in conjunction with VAV
    systems for cooling-only service. Care in design minimizes simul-
    taneous heating and cooling. The section on Variable Air Volume
    has further details.
    Zoning—Interior
    Interior spaces have relatively constant conditions because they
    are isolated from external influences. Cooling loads in interior
    zones may vary with changes in the operation of equipment and
    appliances in the space and changes in occupancy, but usually inte-
    rior spaces require cooling throughout the year. A VAV system has
    limited energy advantages for interior spaces, but it does provide
    simple temperature control. Interior spaces with a roof exposure,
    however, may require similar treatment to perimeter spaces requir-
    ing heat.
    Space Heating
    Although steam is an acceptable medium for central system pre-
    heat or reheat coils, low-temperature hot water provides a simple
    and more uniform means of perimeter and general space heating.
    Inpidual automatic control of each terminal provides the ideal space comfort. A control system that varies the water temperature
    inversely with the change in outdoor temperature provides water
    temperatures that produce acceptable results in most applications.
    To produce the best results, the most satisfactory ratio can be set
    after the installation is completed and actual operating conditions
    are ascertained.
    Multiple perimeter spaces on one exposure served by a central
    system may be heated by supplying warm air from the central sys-
    tem. Areas that have heat gain from lights and occupants and no heat
    loss require cooling in winter, as well as in summer. In some sys-
    tems, very little heating of the return and outdoor air is required
    when the space is occupied. Local codes dictate the amount of out-
    side air required (see ASHRAE Standard 62 for recommended opti-
    mum outside air ventilation). For example, with return air at 24°C
    and outside air at  18°C, the temperature of a 25% outdoor/75%
    return air mixture would be 13°C, which is close to the temperature
    of the air supplied to cool such a space in summer. In this instance,
    a preheat coil installed in the minimum outdoor airstream to warm
    the outdoor air can produce overheating, unless it is sized so that it
    does not heat the air above 2 to 5°C. Assuming good mixing, a pre-
    heat coil located in the mixed airstream, prevents this problem. The
    outdoor air damper should be kept closed until room temperatures
    are reached during warm-up. A return air thermostat can terminate
    the warm-up period.
    When a central air-handling unit supplies both perimeter and
    interior spaces, the supply air must be cool to handle the interior
    zones. Additional control is needed to heat the perimeter spaces
    properly. Reheating the air is the simplest solution, but it is not
    acceptable by most energy codes. An acceptable solution is to vary
    the volume of air to the perimeter and combine it with a terminal
    heating coil or a separate perimeter heating system, either base-
    board, overhead air heating, or a fan-powered terminal unit with
    supplemental heat. The perimeter heating should be inpidually
    controlled and integrated with the cooling control. Resetting the
    supply water temperature downward when less heat is required gen-
    erally improves temperature control. For further information, refer
    to Chapter 12 in this volume and Chapter 45 of the ASHRAE Hand-
    book—Applications.
     
    Temperature Versus Air Quantity
    Designers have considerable flexibility in selecting the supply
    air temperature and corresponding air quantity within the limita-
    tions of the procedures for determining heating and cooling loads.
  1. 上一篇:水力碎浆机英文文献和参考文献
  2. 下一篇:回收塑料材料注射成型英文文献和中文翻译
  1. 汽车内燃机连杆载荷和应...

  2. 机械手系统英文文献和中文翻译

  3. 固体氧化物燃料电池英文文献和中文翻译

  4. 船舶运动仿真系统英文文献和中文翻译

  5. 兰州某大酒店空调设计+CAD图纸

  6. 新能源空调系统设计英文文献和中文翻译

  7. 正交试验回归法和响应曲...

  8. 浅析中国古代宗法制度

  9. 中国传统元素在游戏角色...

  10. 高警觉工作人群的元情绪...

  11. NFC协议物理层的软件实现+文献综述

  12. 江苏省某高中学生体质现状的调查研究

  13. g-C3N4光催化剂的制备和光催化性能研究

  14. 巴金《激流三部曲》高觉新的悲剧命运

  15. 上市公司股权结构对经营绩效的影响研究

  16. C++最短路径算法研究和程序设计

  17. 现代简约美式风格在室内家装中的运用

  

About

优尔论文网手机版...

主页:http://www.youerw.com

关闭返回