摘要电力系统中性点接地方式是事关电力系统安全运行的一项重要应用技术。过去我国沿用苏联模式,中、低压电网主要采用中性点不接地方式。近年来随着城市用电规模的扩大,特别是城市电缆线路增多,中性点不接地系统发生单相接地以后,接地电流明显增大。为了能够及时灭弧,许多系统采用中性点经消弧线圈或小电阻接地方式。 本文研究一种基于可控电抗器原理的消弧线圈方案,以同时实现补偿流经单相接地故障点的接地电容电流和接地泄漏电导电流,文中从理论上论证了这种消弧线圈原理的正确性,并通过Matlab/Simulink仿真加以验证。61046
毕业论文关键词:消弧线圈 接地方式 Matlab/Simulink
Title Modeling and analysis of Arc suppression coil grounding device
Abstract The grounding method of Power system neutral point is an important for safe operation of power system. In recent years, with the expansion of city electricity, especially with the increases of the city of cable line, after isolated neutral system coming about single phase grounding, the grounding current is increased obviously. In order to arc extinguishing timely, many systems use the neutral point grounding method with the Petersen coil or small resistance. Based on the summary of the research achievements of arc suppression coil, a type of arc suppression coil is proposed on the basis of the principle of controlled reactor. It can realize the compensation of grounding capacitive current and leakage conductance current through The single phase grounding fault point at the same time. It demonstrates the correctness of the principle of arc suppression coil from theory and Matlab/Simulink simulation.
Key word:Arc suppression coil;Grounding method ; Matlab/Simulink
目 录
1 绪论 1
1.1 引言 1
1.2 各种接地方式的对比 . 1
1.2.1 中性点不接地 . 1
1.2.2 经小电阻接地 . 2
1.2.3 中性点经消弧线圈接地方式 . 2
2 中性点经消弧线圈补偿电网的运行原理 3
2.1 中性点经消弧线圈补偿电网的正常运行分析 . 3
2.2 中性点经消弧线圈补偿电网的故障运行分析 . 5
2.3 消弧线圈在补偿电网中的运行状态 . 7
2.4 中性点经消弧线圈补偿电网的对地电容电流检测 7
3 自动跟踪补偿消弧线圈的结构及实现原理 9
3.1 双绕组可控电抗器分析 9
3.2 多绕组大容量可控电抗器分析 . 10
3.2.1 多绕组变压器模型的建立 . 10
3.2.2 大容量可控电抗器的实现原理 . 11
3.3 自动跟踪补偿消弧线圈的实现原理 . 12
3.3.1 消弧线圈的结构 . 12
3.3.2 消弧线圈自动跟踪补偿原理 . 13
4 自动跟踪补偿消弧线圈控制部分的建模与仿真 . 15
4.1 消弧线圈的电流跟踪控制技术 . 15
4.2 滞后移相控制电路的设计 . 18
5 经消弧线圈接地系统的仿真建模 . 20
5.1 参数和仿真图 . 20
5.2 消弧线圈系统的仿真结果及分析 . 22 消弧线圈接地装置的建模与分析:http://www.youerw.com/zidonghua/lunwen_66652.html