摘要本次设计的设计的是上海市茂业物流公司办公楼中央空调系统,让室内环境得到更好的净化并且使员工能够在这样的办公环境中好好工作。建筑共七层,总面积为4955m²,首层净高3.8m,其他层净高均为3.5m。要求采用空调夏季制冷冬季供暖。末端采用风机盘管送新风系统,制冷方面用了冷水机组制冷。
通过负荷计算计算空调系统,并对风机盘管进行选型,选出空调系统的方案等等;空调系统的划分与系统方案的确定;冷源的选择;风系统的设计与计算;室内送风方式与气流组织形式的选定;水系统的设计、布置与水力计算; 风管系统与水管系统保温层的设计等内容。除此之外我的设计中还包含了空调的末端装置和空调系统的选取。而选定室内风管和水管的位置还基于建筑的的结构和我们选取空调系统的特点。19967
关键词:办公楼,中央空调,水冷机组,风机盘管加新风系统
General information
The design of central air.conditioning system for the Maoye logistics building of a shanghai company is aimed to get a comfortable working condition indoors. The total area of the building is 4955 m². The height of the first floor is 3.8 meters,and the other floor’heights are all 3.5meters. The air.condition system is designed to supply cool air in summer, and a fan coil units (FCUs)..fresh air system is selected and central screw water chillers are used to provide the chilling water needed.
Some of the main points in this design are given as follows:
To design an appropriate air.conditioning system for the building, the overall analysis is important. This includes the calculation, such as cooling load calculation, the estimation of system zoning; the design of air duct system and calculation; the estimation of air distribution method and the selection of relevant equipments; the design of water system and the analysis of its resistance losses; the plan of the insulation of air duct and chilled water pipes; etc.. Meanwhile, equipment selection is also an essential part of the design. According to the requirement, a fan coil units (FCUs)..fresh air system is appropriate. Thus,the main process equipment, i.e.
KEY WORDS: official building, central air conditioning, cooling water chiller
fan coil units (FCUs)..fresh air system
目 录
第一章 绪 论 1
第二章 系统方案的选择确定 2
第三章 工程概况 3
3.1建筑相关资料 4
3.2室外设计参数 4
3.3室内设计参数 5
第四章 空调负荷计算 6
4.1围护结构瞬变冷负荷计算原理 6
4.1.1外墙和屋面瞬变传热引起的冷负荷 6
4.1.2室内传热文护瞬时冷负荷 6
4.1.3外窗瞬变传热引起的冷负荷 7
4.1.4设备散热形成的冷负荷 7
4.1.5新风冷负荷 9
4.2办公楼围护结构冷负荷计算 9
4.3各房间送风方式的确定 12
4.4 办公楼新风量和新风负荷的确定 13
4.4.1新风负荷计算举例 13
4.4.2办公楼新风冷负荷计算书 14
第五章 风机盘管加新风系统选型计算 15
5.1风机盘管系统选型计算 16
5.2新风机组的选型 18
第优尔章 空调风系统 21
6.1空调房间气流组织 21
6.2风口的布置 21
6.2.1新、排风口的防雨百叶尺寸的确定 21
6.2.2风管阀门的选择 21
6.2.3送风口的布置原则 22 茂业物流公司办公楼空调设计+CAD图纸:http://www.youerw.com/gongcheng/lunwen_11563.html