3-4 16.34 DN70 4.23 1.287 241.07 2158.444 0.3 248.606 2407.05
4-5 15.65 DN70 4.19 1.223 200.6 2336.164 0.3 228.053 2564.217
5-6 14.96 DN70 4.20 1.179 163.84 2153.055 0.3 208.387 2361.442
6-7 14.27 DN70 5.60 1.124 130.74 2629.433 0.3 189.607 2819.04
7-8 13.58 DN70 4.10 1.071 239.90 2031.666 0.3 171.714 2203.38
8-9 12.89 DN70 4.78 1.106 178.47 1858.675 0.3 154.708 2013.383
9-10 11.51 DN70 4.67 0.907 126.01 1473.371 0.3 123.355 1596.726
10-11 10.13 DN70 6.23 0.798 82.53 1165.26 0.3 95.55 1260.81
11-12 9.3 DN70 4.11 0.733 169.65 874.947 0.3 80.533 955.48
12-13 8.07 DN70 4.10 0.635 290.84 675.78 0.3 60.64 736.42
13-14 6.15 DN50 4.19 0.906 78.79 1981.696 0.3 123.104 2104.80
14-15 4.77 DN50 4.20 0.703 285.19 1247.014 0.3 74.056 1321.07
15-16 2.71 DN40 4.21 0.600 169.65 1217.85 0.3 53.83 1271.68
16-17 1.52 DN32 4.20 0.444 290.84 848.64 0.3 29.56 878.20
17-18 0.83 DN32 4.31 0.242 78.79 297.75 0.3 8.81 306.56
18-19 0.83 DN32 2.46 1.310 285.19 169.95 0.3 8.81 178.76
合计 26266.2 2399.413 28666.04
6.3 冷凝水管设计
由于各种空调设备如风机盘管、新风机组、空调机组等在运行的过程中产生的冷凝水,必须及时予以排走。排放冷凝水的管道设计,应注意以下各要点:水流方向,水平管道应保持不小于千分之一的坡度,且不允许有积水部位;为了防止冷凝水管道表面产生结露,必须进行防结露验算;冷凝水立管的顶部应设计通向大气的透气管。冷凝水管的公称直径,应根据末端设备的冷量进行确定。一般情况下,每千瓦冷负荷每小时大约产生0.4Kg左右的冷凝水;在潜热负荷较高的场合,每千瓦冷负荷每小时大约产生0.8Kg左右的冷凝水。
- 上一篇:七层酒店客房中央空调系统设计+CAD图纸
- 下一篇:十二层公司办公楼中央空调系统设计+CAD图纸
-
-
-
-
-
-
-
高警觉工作人群的元情绪...
g-C3N4光催化剂的制备和光催化性能研究
浅析中国古代宗法制度
江苏省某高中学生体质现状的调查研究
C++最短路径算法研究和程序设计
上市公司股权结构对经营绩效的影响研究
中国传统元素在游戏角色...
巴金《激流三部曲》高觉新的悲剧命运
NFC协议物理层的软件实现+文献综述
现代简约美式风格在室内家装中的运用