摘要继电保护作为电网安全生产体系的重要环节,在电力安全生产中起着重要的作用。继电保护的快速性,可靠性及灵敏性在很大程度上取决于保护装置本身的可靠性和保护整定值设置的合理性。
这里对于600MW发电机组继电保护自动装置给定的原始数据及技术要求,确定电气的主接线,然后根据短路点位置计算短路点最大运行方式和最小运行方式下的短路电流,再由电路特点,对发电机变压器组自动装置进行继电保护的整定配置,由整定原则并依次计算出整定值。本文采用了先进的微机式准同期自动装置、微机备用电源快速投入装置WBKQ-01B和快速电源切换装置等设备,并对各个装置进行整定计算,鲜明的突出各个保护的特点及保护范围。64486
毕业论文关键词 短路计算 继电保护 自动装置 整定计算 整定原则
毕业设计说明书(论文)外文摘要
Title The Setting Calculation of 600 MW Generator Relay Protection Automatic Device
Abstract
Relay protection is an important part of production safety system of power grid,it plays an important role in the safe production of power. The fast , reliability and sensitivity of the relay protection depends largely on its rationality to protect the device reliability and protection setting value set.
Here for the original data and technical requirements,of 600MW generator relay protection automatic device is given to determine the main electrical wiring. Then calculate the short-circuit current according to the fault locations .According to the circuit characteristics we can do the setting calculation of the generator transformer set automatic device.and then according to the setting principle calculated the setting value .This paper adopts the advanced microcomputer quasi-synchronizing automatic device ,reserving power supply fast switching device WBKQ-01B and quick power input device.And for each device does the setting calculation.Prominent the features and protection scope.
Keywords short-circuit calculation relay protection automatic device setting calculation setting principle
目 次
1. 绪论 1
2. 发电机组的一次设备设计说明 2
2.1 600MW发电机组的一次接线及系统运行方式 2
2.2 主要设备参数 2
2.3 发电机组安全自动装置配置 2
2.3.1备用电源(备用设备)自动投入装置 3
2.3.2自动准同期装置 3
2.3.3微机备用电源快速切换装置 3
2.4 发电机组继电保护保护装置 3
3 短路电流计算 4
3.1 600MW发电机组一次接线及系统运行方式说明 4
3.2 各元件主要参数的计算 4
3.3 短路电流和短路阻抗的计算 5
3.4 K1点故障短路计算 8
3.4.1正序 8
3.4.2零序 10
3.4.3最大运行方式下短路计算 11
3.4.4最小运行方式下短路计算 12
3.5 K2点故障短路计算 600MW发电机组继电保护自动装置整定计算+电路图:http://www.youerw.com/zidonghua/lunwen_71679.html