摘要本文为镇江市某医院综合楼空调工程设计计算书。经计算建筑空调面积约15000㎡,总冷负荷约为1700kW,总热负荷为1500kW。经分析比较,本设计采用
冷水机组和热水锅炉(来自医院锅炉房)作为冷热源。一般房间室内空调方案为风机盘管加独立新风系统,手术室使用全空气系统。洁净手术室采用局部单向流,上部中间区域送分,下部两侧回风。本设计所有图纸均由计算机软件AutoCAD绘制并输出,共计完成图纸27张。5767
关键词 空调工程设计 风机盘管 洁净手术室
毕业设计说明书(论文)外文摘要
Title HVAC Design of One Comprehensive Building of a Hospital in Zhenjiang
Abstract
This article is the design expression of the HVAC Design of One Compreensive Building of a Hospital in Zhenjiang. Calculated,the using air-condition area is about 15000m2,and building cooling load is about 1700kW,and heating load is 1500kW;Through the analysis, cold water chiller and boiler system(from a hospital boiler house) are used as the cold and heat sources of the building.To most rooms,the air condition systerm use the fan coil plus an independent air condition systerm,and the operating room use all air systerm.The clean rooms use part uniflow,senting air from the centre zone at the top,returning air to the bottom oftwo sides.All the drawings are drawn and printed by using AutoCAD.In total,there are 27 drawings accomplished.
Keywords HVAC Design fan coil clean rooms
目 次
1 工程概况 1
2 设计参数 1
2.1 建筑围护结构 1
2.2 室外气象设计参数 1
2.3 室内设计参数 1
3 空调负荷计算 2
3.1 空调冷负荷计算 2
3.2 房间冷负荷计算举例 5
3.3 湿负荷计算 6
3.4 空调冷负荷汇总 6
3.5 空调热负荷计算 9
3.6 房间热负荷计算举例 10
3.7 空调热负荷汇总 10
4 空调方式设计 11
4.1 空调系统形式选择 11
4.2 风机盘管及新风机组选择 12
5 气流组织 14
6 手术室净化空调系统设计 15
6.1 风量计算 15
6.2 系统划分及设备选型 16
6.3 风口布置及气流组织 16
6.4 空气处理方案 17
6.5 分管布置 17
7 空调系统水力计算 17
7.1 水系统水力计算 17
7.2 风系统水力计算 19
8 空调系统冷热源设计 19
8.1 冷热源方案 19
8.2 设备选型 20
9 防排烟系统设计 21
结论 23
致谢 24
参考文献 25
1 工程概况
本次设计为镇江市某医院综合楼的空调工程设计,该综合楼地上二十二层,地下一层。其中地下一层为设备用房,一至三层为诊疗室及各种检查、化验室,四、五层为手术室及术后恢复用房,其中间为设备夹层,优尔至二十二层病房及诊疗、会议室等用房。全楼的空调面积约为15000㎡。
2 设计参数
2.1 建筑围护结构
该建筑的建筑围护结构传热系数见下表2.1。
表2.1 建筑围护结构参数
结构形式 结构材料 传热系数 W/(m.k) 医院综合楼空调工程设计计算书:http://www.youerw.com/gongcheng/lunwen_2946.html