摘要本工程为长沙市博物馆,该馆建筑占地面积1546.71m2,总建筑面积为4736.8m2,地下建筑面积为1908.86m2,地上建筑面积为2827.94m2,建筑总高度为11.48m。根据室内温湿度要求,中央空调设计分为恒温恒湿空调与舒适性空调。本设计采用风冷式热泵作为空调冷热源。文物专题展厅、文物库房、唐墓壁画室等采用全空气系统,办公区、休息室、报告厅等采用了风机盘管加独立新风系统。全空气系统选用方型散流器平射流形式,而风机盘管加独立新风系统有百叶风口顶送的形式。水系统采用闭式水平异程垂直异程。卫生间通风统一由排风扇接出,在末端安装止回阀。临时展览区设置防排烟系统,选用变速风机,平时排风,发生火灾时排烟。66183
毕业论文关键词:全空气系统 风机盘管加独立新风系统 防排烟
毕业设计说明书(论文)外文摘要
TitleThe central air conditioning design of Changsha museum
Abstract This project is in Changsha Citymuseum, the museum building covers an area of 1546.71 m2, total construction area of 4736.8 m2, underground construction area of 1908.86 m2, construction area of 2827.94 m2 on the ground, building a total height of 11.48 m.According to indoor temperature and humidity requirements, pided into the constant temperature and humidity air conditioning and the comfort air conditioning.This design adopts the air-cooled heat pump air conditioning as cold and heat source. Cultural relics of the thematic exhibition hall, storage, tang tomb murals chamber adopts full air system, office, lounge, lecture hall, etc. adoptsthe fan coil plus fresh air system independently.
KeywordsAll air systemFan coil plus fresh air system independently Smoke control
目 录
1 概论
1.1 工程概况 1
1.2 设计依据 1
1.2.1 设计目的 1
1.2.2 设计任务及要求 1
1.2.3 设计规范与标准 1
2 空调负荷计算 1
2.1 空调室内、外计算参数 1
2.1.1 室内空气设计参数 1
2.1.2 空调室外空气计算参数 2
2.1.3 土建资料 2
2.2 空调新风量的确定 2
2.3 空调冷负荷计算 2
2.3.1 维护结构瞬变传热引成的冷负荷 3
2.3.2 透过玻璃窗的日射得热引成的冷负荷 4
2.3.3 室内热源散热引成的冷负荷 5
2.3.4 空调夏季新风负荷计算 5
2.4 湿负荷计算 6
2.5 空调热负荷计算 6
2.5.1 围护结构基本耗热量计算 6
2.5.2 空调冬季新风热负荷计算 7
2.6 空调负荷计算结果汇总与分析 7
3 空调系统冷热源的设计 8
3.1 冷热源系统设计的一般要求 8
3.2 空调冷热源的分类