毕业论文

打赏
当前位置: 毕业论文 > 自动化 >

企业10KV变电所及低压配电系统的设计(11)

时间:2017-05-07 20:41来源:毕业论文
=0.08 5 (0.4/10.5)2 =0.5(m) (2)电力变压器的阻抗: RTˊ=△PK(UB2/SNT)2 (5-11) =14500(0.4/1600)2 =0.91(m) X Tˊ=(UK/100)(UC22/SNT) (5-12) =(4.5/100) (0.42


=0.08 5 (0.4/10.5)2
=0.5(mΩ)
(2)电力变压器的阻抗:
RTˊ=△PK(UB2/SNT)2                                                                                                (5-11)
=14500×(0.4/1600)2
=0.91(mΩ)
X Tˊ=(UK/100)(UC22/SNT)                                             (5-12)
=(4.5/100)  (0.42/1600)
=4.5(mΩ)
其等值电路为图:
 
图5-2  T1、T2低压侧短路计算等效电路图
得k-2点短路电路总阻抗为:
R(K-2)=RL’+RT’                                                          (5-13)
=0.91+0.7
=1.61(mΩ)
X(K-2)=XL’+XT’                                                          (5-14)
=4.5+0.5
=5(mΩ)
(4)求三相短路电流周期分量有效值
I(3)(K-2)=UB22/ ( )                              (5-15)
=17.6KA
(5)三相短路冲击电流及第一个短路全电流的有效值
ksh=1+e- =1.36                                                   (5-16)
i(3)sh= KshI(3)(K-2)                                                     (5-17)
= 17.6
=33.9KA
I(3)sh= I(3)(K-2)                                          (5-18)
=17.6 1.12
=19.7KA
I’’(3)=I(3) =I(3)(K-2)=17.6KA                                              (5-19)
(6)三相短路容量
S(3)(K-2)=  UB2I(3)(K-2)                                                   (5-20) 企业10KV变电所及低压配电系统的设计(11):http://www.youerw.com/zidonghua/lunwen_6642.html