= 17.6
=12.2MVA
2、T3变压器:Uk % = 4.5
1)高压侧短路电流及短路容量与T1变压器相同,这里不再赘述。
2) 低压侧:
(1)电力电缆的阻抗(需折算至低压侧)
x0 =0.08 Ω/km, r0 =0.09Ω/km,l=5km.
RL’=lr0/(UB1/UB2)2
=0.09 5 (0.4/10.5)2
=0.7(mΩ)
XL’= lx0/(UB1/UB2)2
=0.08 5 (0.4/10.5)2
=0.5(mΩ)
(2)电力变压器的阻抗:
RTˊ=△PK(UB2/SNT)2
=6200×(0.4/630)2
=2.5(mΩ)
X Tˊ=(UK/100)(UB22/SNT)
=(4.5/100) (0.42/630)
=11.4(mΩ)
其等值电路为图:
图5-3 T3低压侧短路计算等效电路图
得k-2点短路电路总阻抗为:
R(K-2)=RL’+RT’
=0.7+2.5
=3.2(mΩ)
X(K-2)=XL’+XT’
=11.4+0.5
=11.9(mΩ)
(4)求三相短路电流周期分量有效值
I(3)(K-2)=UB22/ ( )
=7.5KA
(5)三相短路冲击电流及第一个短路全电流的有效值
ksh=1+e- =1.43
i(3)sh= KshI(3)(K-2)
= 7.5
=15.2KA
I(3)sh= I(3)(K-2)
=15.2 1.17
=17.8KA
I’’(3)=I(3) =I(3)(K-2)=7.5KA
(6)三相短路容量
S(3)(K-2)= UB2I(3)(K-2)
= 7.5
=5.2KVA
3、T4变压器:Uk % = 4